Product Description
BAC-IO9 has been designed to be a compact wall mounted BACnet MS/TP input and output module.The module has 2 volt-free digital inputs for measurements e.g. for windows, occupancy sensors and so on. The module has 2 digital outputs, 24Vac triacs switching the plant items on/off.
The Modules has 2 universal inputs for measuring NTC10 temperature, resistive measurements (e.g. light level) or volt-free on/off signals.
The three analogue 0..10Vdc outputs complete the compact IO-module. With the analogue outputs it is possible to control zonevalves and other modulating plant equipment.
The module supports BACnet MS/TP communications with most commonly used baud rates and parity settings. The module also supports BACnet device and object discovery allowing fast and efficient programming.
Product Info Sheet
Specifications
-Power Supply 24Vac/dc -10%/+15%
– Standards CE Directive 2004/108/EY
EN61000-6-3: 2001 (Generic Emission)
EN61000-6-1: 2001 (Generic Immunity).
– Degree of Protection IP20
POWER
– ARM 9 S3C2410 400MHz Main Processor
– M3 Cortex Processor for the I/O
– 16 Mbyte NOR Flash
– 64 Mbyte SDRAM
COMMUNICATION
–BACnet Communications
-Protocol BACnet MS/TP
-Interface RS485; maximum 63 devices
– MAC Addressin 0..63 via a bit switch; 0..247 via tool / network
– Communication 9k6/19k2/38k4/76k8 Baud; Parity None/Even/Odd, 1 or 2 Stop
Bits (baud rate adjustable through bit switch)
DEVICE INPUTS & OUTPUTS
-Analogue Outputs 3 x 0..10V < 5mA; 100k min impedance for 1% accuracy
-Digital Outputs 2 x 24Vac Triacs; 2A maximum; requires 24Vac Power Supply
-Signal Inputs
-Resistive Inputs 2 x Universal NTC10/Resistive/Digital Inputs, 0..50kOhms
(NTC10/Volt-Free Digital default, configurable via
SW-DCT-USB tool to resistive mode)
-Digital Inputs 2 x Volt-Free Contact, Impedance <1KOhm





Reviews